BKG500 input/output module (hereinafter referred to as module) is a new Module. It is mainly used to connect the fire control linkage equipment which needs to be controlled by Fire Alarm controller. The field application is mainly connected with 220V cutting, fan and water pump and other equipment.
1. Working voltage:
Rated working voltage: DC24V allowable range: 14V ~ 28V
2. Working current:
Monitor current ≤0.2mA Start current ≤0.5mA
3. Input check line: when the input line is short circuit or open circuit, the module will send fault signal to the control panel
4. Output check line: when the output line is short circuit or open circuit, the module will send fault signal to the control panel
5. Output contact capacity: passive output, capacity of AC220V/1A
6. Indicator light: red (input indicator light: bright during inspection, often on action; Output indicator light: often on after startup)
7. Encoding mode: electronic encoding mode by encoder, occupying a address, encoding range can be arbitrarily set between 1 and 255
8. Use environment:Atmospheric pressure: 86kPa ~ 106kPa;Temperature: -10℃ ~ +55℃
Relative humidity ≤95%, no condensation
9. Dimensions: 86mm×86mm×40mm(with bottom shell)
10. Shell material and color: ABS, porcelain white
11. Weight: about 147g(with base)
12. Installation hole spacing: 60mm